Which of the following is an advantage of Newton-Raphson method

Electrical Engineering MCQ Which of the following is an advantage of Newton-Raphson (NR) method: Correct answer: 3. Both of these Explanation: The Newton-Raphson (N-R) method is an iterative numerical technique used for solving nonlinear algebraic equations, and it is commonly applied in power system analysis for solving load flow problems. The advantages of the N-R … Read more

Ferranti effect can be compensated by using

Ferranti effect can be compensated by using: Correct answer: 3. Shunt reactors Explanation: When medium or long electric power transmission lines are operated at no-load or light-load conditions, the receiving-end voltage becomes more than the sending-end voltage. The phenomenon of rise in voltage at the receiving-end of a transmission line during no load or lightly … Read more

If the primary fault current is 2000 A, the relay setting is 50% and CT ratio is 400 : 5, then plug setting multiplier will be – Electrical Engineering MCQ

Electrical Engineering MCQ If the primary fault current is 2000 A, the relay setting is 50% and CT ratio is 400 : 5, then plug setting multiplier will be: Current answer: 4. 10 Explanation: Pick up Value = Rated secondary current of CT × Current Setting = 5 × 0.5 = 2.5 A Fault current … Read more