Discrete I/O Capability of PLC

Input/output  capability  for  programmable  logic controllers  comes  in  three  basic  varieties: discrete, analog, and network.

A “discrete” data point is one with only two states on and off. Process switches, pushbutton switches, limit switches, and proximity switches are all examples of discrete sensing devices. In order for a PLC to be aware of a discrete sensor’s state, it must receive a signal from the sensor through a discrete input channel. Inside each discrete input module is (typically) a set of light-emitting diodes (LEDs) which will be energized when the corresponding sensing device turns on. Light from each LED shines on a photo-sensitive device such as a phototransistor inside the module, which in turn activates a bit (a single element of digital data) inside the PLC’s memory. This opto-coupled arrangement makes each input channel of a PLC rather rugged, capable of isolating the sensitive computer circuitry of the PLC from transient voltage “spikes” and other electrical phenomena capable of causing damage:

The internal schematic diagram for a discrete input module (“card”) shown above reveals the componentry  typical  for a single  input  channel on that  card.   Each input  channel has its  own optocoupler, writing  to  its  own unique memory register  bit inside the  PLC’s  memory.  Discrete input cards for PLCs typically have 4, 8, 16, or 32 channels.

Indicator  lamps, solenoid  valves,  and motor  starters  (assemblies  consisting  of contactors  and overload protection  devices)  are  all examples of discrete  control  devices.   In a manner similar  to discrete inputs,  a PLC connects to any number of different discrete final control devices through a discrete output channel. Discrete output modules typically use the same form of opto-isolation to allow the PLC’s computer circuitry to send electrical power to loads: the internal PLC circuitry driving an LED which then activates some form of photosensitive switching device. Alternatively, small electromechanical relays may be used in lieu of opto-isolating semiconductor switching elements such as transistors (DC) or TRIACs (AC):

As  with  the  schematic  diagram for a discrete  input  module  shown previously, the  schematic diagram shown  here for a discrete  output  module  reveals  the  componentry  typical  for a single channel on that  card.  Each output  channel has its  own optocoupler, driven by its  own unique memory register bit inside the PLC’s memory. Discrete output cards for PLCs also typically have

4, 8, 16, or 32 channels.

An important concept to master when working with DC discrete I/O is the distinction between current-sourcing  and current-sinking  devices.   The terms  “sourcing”  and “sinking”  refer to  the direction of current (as denoted by conventional flow notation) into or out of a device’s control wire. A device sending (conventional flow) current out of its control terminal to some other device(s) is said  to  be sourcing  current,  while  a device  accepting (conventional  flow) current  into  its  control terminal is said to be sinking  current.

To illustrate,  the following illustration shows a PLC output channel is sourcing  current to an indicator lamp, which is sinking  current to ground:

These  terms  really only make  sense when electric current  is  viewed from the  perspective  of conventional  flow, where the  positive  terminal  of the  DC power supply  is  envisioned  to  be the “source” of the current,  with current finding its way “down” to ground (the negative terminal of the DC power supply).  In every circuit formed by the output channel of a PLC driving a discrete control device, or by a discrete sensing device driving an input channel on a PLC, one element in the circuit must be sourcing current while the other is sinking current.

An engineering colleague of mine has a charming way to describe sourcing and sinking:  blowing and sucking.  A device that sources current to another “blows” current toward the other device. A device that sinks current “sucks” current from the other device. Many students seem to find these terms  helpful in first  mastering  the  distinction  between sourcing  and sinking  despite  (or perhaps because of !) their informal nature.

If the discrete device connecting to the PLC is not polarity-sensitive,  either type of PLC I/O module will suffice. For example, the following diagrams show a mechanical limit switch connecting to a sinking PLC input and to a sourcing PLC input:

Note the differences in polarity and labeling between the sinking card’s common terminal and the sourcing card’s common terminal.  On the “sinking” card, the input channel terminal is positive while the common (“Com”) terminal is negative.  On the “sourcing” card, the input channel terminal is negative while the common (“VDC”) terminal is positive.

Some discrete sensing devices are polarity-sensitive, such  as electronic proximity sensors containing transistor outputs.  A “sourcing” proximity switch can only interface with a “sinking” PLC input channel, and vice-versa:

In all cases, the “sourcing” device sends current out of  its signal terminal while the “sinking”

device takes current into its signal terminal.

Two photographs of a DC (sinking) discrete input module for an Allen-Bradley model SLC 500 PLC are shown here: one with the plastic cover closed over the connection terminals, and the other with  the  plastic  cover opened up for viewing the  terminals.   A legend on the  inside of the  cover shows the purpose of each screw terminal:  eight input channels (numbered 0 through 7) and two redundant “DC Com” terminals for the negative pole of the DC power supply to connect:

A standard feature found on practically every PLC discrete I/O module is a set of LED indicators visually  indicating  the  status  of each bit (discrete  channel). On the  SLC 500 module, the  LEDs appear as a cluster of eight numbered squares near the top of the module.

A photograph of discrete output terminals on another brand of PLC (a Koyo model DL06) shows somewhat different labelling:

Here, each output channel terminal is designated with a letter/number code beginning with the letter “Y”. Several “common” terminals labeled with “C” codes service clusters of output channels. In this  particular  case, each “common”  terminal  is  common only to  four output  channels.  With sixteen total output channels on this PLC, this means there are four different “common” terminals. While this may seem somewhat strange (why not just have one “common” terminal for all sixteen output channels?), it more readily permits different DC power supplies to service different sets of output channels.

Electrical polarity is not an issue with AC discrete I/O, since the polarity of AC reverses periodically anyway.   However, there  is  still  the  matter  of whether the  “common”  terminal  on a discrete  PLC module  will  connect to  the  neutral  (grounded) or hot (ungrounded) AC  power conductor.

The next photograph shows a discrete AC output module for an Allen-Bradley SLC 500 PLC, using TRIACs as power switching devices rather than transistors as is customary with DC discrete output modules:

This particular eight-channel module provides two sets of TRIACs for switching power to AC loads, each set of four TRIACs receiving AC power from a “hot” terminal (VAC  1 or VAC 2), the other side of the load device being connected to the “neutral” (grounded) conductor of the AC power source.

Fortunately, the hardware reference manual supplied by the manufacturer of every PLC shows diagrams illustrating how to connect discrete input and output channels to field devices.  One should always consult these diagrams before connecting devices to the I/O points of a PLC!


Article from Lessons In Industrial Instrumentation by Tony R. Kuphaldt – under the terms and conditions of the Creative Commons Attribution 4.0 International Public License