Switchgear and Protection MCQs Part 10
Contents
- 1 An arc is produced when switch having high voltage and large current circuit is
- 2 A circuit breaker is rated as 1500 A, 1000 MVA, 33 kV, 3 second, 3 phase oil circuit breaker. The short time rating is
- 3 The rated secondary current of current transformer for relays is usually
- 4 Which of following is correct about back-up protection
- 5 A 60 Hz, 33 kV, 3-phase alternator with earthed neutral has reactance of 5 ohms per phase and is connected to bus-bar through a circuit breaker
An arc is produced when switch having high voltage and large current circuit is
An arc is produced when switch having high voltage and large current circuit is
- Closed
- Opened
- Either of above
- None of above
Correct answer: 2. Opened
A circuit breaker is rated as 1500 A, 1000 MVA, 33 kV, 3 second, 3 phase oil circuit breaker. The short time rating is
A circuit breaker is rated as 1500 A, 1000 MVA, 33 kV, 3 second, 3 phase oil circuit breaker. The short time rating is:
- 15236.66 A for 3 seconds
- 20994.55 A for 3 seconds
- 22342.48 A for 3 seconds
- 25669.55 A for 3 seconds
Correct answer: 2. 20994.55 A for 3 seconds
Solution: Rated symmetrical breaking current = (1200 * 10^6)/(√3 * 33 * 10^3) = 20994.55 A for 3 seconds
The rated secondary current of current transformer for relays is usually
The rated secondary current of current transformer for relays is usually:
- 2.5 A
- 5 A
- 10 A
- 20 A
Correct answer: 2. 5 A
Which of following is correct about back-up protection
Which of following is correct about back-up protection:
- It operates when primary protection fails
- It is second line of defense
- When back-up protection operates a large portion of system disconnects
- All of these
Correct answer: 4. All of these
A 60 Hz, 33 kV, 3-phase alternator with earthed neutral has reactance of 5 ohms per phase and is connected to bus-bar through a circuit breaker
A 60 Hz, 33 kV, 3-phase alternator with earthed neutral has reactance of 5 ohms per phase and is connected to bus-bar through a circuit breaker. Distributed capacitance upto circuit breaker between phase and neutral is 0.01 µF. The frequency of oscillations is:
- 12500 Hz
- 13852 Hz
- 14990 Hz
- 15672 Hz
Correct answer: 2. 13852 Hz
Solution:
Inductance per phase L = XL/2πf = 5/(2π * 60) = 0.0132 H
Capacitance per phase, C = 0.01 µF = 0.01 * 10^-6 F
————————
Frequency of oscillations
f = 1/2π√LC
f = 1/2π√0.0132 H * 0.01 µF = 13852 Hz